左光恒, 戴少鹏, 张盛飞, 许坤, 韩强. 法兰连接预制拼装双柱式桥墩抗震性能研究[J]. 北京工业大学学报, 2022, 48(5): 496-506. DOI: 10.11936/bjutxb2021090002
    引用本文: 左光恒, 戴少鹏, 张盛飞, 许坤, 韩强. 法兰连接预制拼装双柱式桥墩抗震性能研究[J]. 北京工业大学学报, 2022, 48(5): 496-506. DOI: 10.11936/bjutxb2021090002
    ZUO Guangheng, DAI Shaopeng, ZHANG Shengfei, XU Kun, HAN Qiang. Seismic Performance of Prefabricated Double-column With Flange Connection[J]. Journal of Beijing University of Technology, 2022, 48(5): 496-506. DOI: 10.11936/bjutxb2021090002
    Citation: ZUO Guangheng, DAI Shaopeng, ZHANG Shengfei, XU Kun, HAN Qiang. Seismic Performance of Prefabricated Double-column With Flange Connection[J]. Journal of Beijing University of Technology, 2022, 48(5): 496-506. DOI: 10.11936/bjutxb2021090002

    法兰连接预制拼装双柱式桥墩抗震性能研究

    Seismic Performance of Prefabricated Double-column With Flange Connection

    • 摘要: 为了解决由于新型法兰连接双柱式桥墩形式下的桥梁结构抗震性能不明确导致的无法在工程中应用和推广的问题,采用拟静力试验和有限元模拟的方法,依托实际工程,研究基于内嵌式法兰连接的预制拼装双柱式桥墩的抗震性能. 首先,设计制作1∶3缩尺试件,开展拟静力试验,验证法兰连接双柱式桥墩是否满足所依托的实际工程抗震设计要求;然后,基于ABAQUS软件对试件进行有限元模拟,分析不同时刻结构不同部位的应力应变状态,探究不同参数对法兰连接双柱式桥墩的抗震性能影响. 研究结果表明:基于内嵌式法兰连接的预制拼装双柱式桥墩满足实际工程抗震设计要求,试件先在墩柱顶部形成塑性铰,随后墩柱底部、盖梁中部相继出现塑性铰,但最终盖梁发生冲切破坏;因此,该结构不适用于中高烈度区,如有工程需求应进一步开展抗震性能研究. 法兰连接节点可以较好地将水平力和弯矩传递至墩柱底部,但不属于刚性连接节点;法兰强度对结构影响较小,轴压比增大会提高结构峰值承载力、降低结构延性、提升结构抗剪能力,但对弹性阶段内的刚度没有影响.

       

      Abstract: To solve the problem of not being able to apply and promote the new flange-connected double-column bridge piers in practical engineering due to the unclear seismic performance of the bridge structure, the seismic performance of prefabricated double-column with embedded flange connection was investigated by using the method of proposed static test and finite element simulation relying on the actual engineering background in the paper. First, the 1∶3 specimens were designed and fabricated to verify whether the flange-connected double-column bridge piers meet the actual engineering seismic design requirements through the proposed static test. Then, finite element simulations were established based on ABAQUS software to analyze the stress-strain states of different parts of the structure at different moments and to investigate the effects of different parameters on the seismic performance of the structure. Results show that prefabricated double-column bridge piers with flange connection meet the actual engineering seismic design requirements. The specimens first formed plastic hinges at the top of the piers column, followed by plastic hinges at the bottom of the pier column and the middle of the cover beam, and finally punching damage occurred in the middle of the cover beam. The structure is not suitable for application in areas of medium and high intensity, and further research on seismic performance should be conducted if there is engineering demand. The flange connection node transferred the horizontal force and bending moment to the bottom of the column well, but it was not a rigid connection node. Flange strength had a small effect on the structure. The axial compression ratio increased the peak structural load capacity, reduced the structural ductility and improved the structural shear capacity, but had no effect on the stiffness in the elastic phase.

       

    /

    返回文章
    返回